In a waste-to-energy control room, one figure comes up again and again: 850 °C for 2 seconds. This is the T2S, and it is what authorises, or forbids, feeding waste.

~5 min read · WtE plant operation · Updated 18 June 2026

What the T2S measures

The T2S, or two-second temperature, is the temperature of the combustion gases measured at the furnace outlet, after the last injection of combustion air. The "2 seconds" is the minimum residence time of the gases at that temperature before they leave the chamber.

It is not a comfort setting. It is the physical condition that guarantees the organic molecules in the flue gas have the time and the energy to be fully destroyed before going further into the boiler.

Why exactly 850 °C

The threshold comes from regulation, not from operator preference. The European Industrial Emissions Directive (IED, 2010/75/EU) requires, in its Annex VI, that gases from waste incineration be raised to at least 850 °C for 2 seconds after the last air injection.

At that temperature, held long enough, the most problematic organic compounds, dioxins and furans first, are reliably destroyed. For hazardous waste containing more than 1 % halogenated organic substances, the threshold rises to 1 100 °C. Put plainly: below 850 °C, combustion is not clean, and incineration is not permitted.

Worth remembering: the T2S is not just one indicator among others. It is a permit to operate. Until it is held, feeding waste is not allowed.

What it means for the operator

In practice, waste feeding is interlocked on the T2S. When the two-second temperature drops below 850 °C, the feed hopper gate closes: waste stops going onto the grate. At the same time, the auxiliary burners (gas or oil) start to support the temperature and bring it back above the threshold.

The point of the job is therefore to anticipate, not to react. A good operator feels the T2S drop coming before the interlock trips, and corrects combustion upstream.

What makes the T2S drop

The operator's levers are primary and secondary air, the feed ram, the grate speed, and as a last resort the auxiliary burners. The whole skill is to balance these actions so the T2S stays comfortably above 850 °C without wasting energy or producing CO.

T2S, emissions and continuous monitoring

The T2S does not stand alone. Combustion that drops off drags emissions with it: carbon monoxide, sometimes unburnt matter. That is why it is monitored continuously, alongside the emission limit values (ELVs) measured by the continuous emission monitoring system (CEMS). Exceedances are recorded and counted. Holding the T2S also means holding your emissions.

Why it is learned by doing

The theory fits in one sentence: hold 850 °C for 2 seconds. The reflex is only acquired by operating. Recognising the signs of a T2S about to drop, adjusting air at the right moment, knowing when to let the auxiliary burners do their work: that is built through practice, ideally without putting a real plant at stake.

This is exactly what an operation simulator allows. You watch the T2S change in real time, you deliberately trigger a drift (wet waste, a loss of air), you see the feed gate close then reopen, and you learn to recover. With a tutor on hand to explain the reason behind each behaviour.